Doors.NET Reference Manual
- 250 -
Ethernet Connection
NOTE: The LAN-520 unit must already be programmed with a static IP address, gate-
way, and subnet prior to adding the Network Communication Channel to the PXL gate-
way.
1. Highlight the Communication Channels node in the hardware tree.
2. Click the Network Communication Channel icon.
3. A channel named New Channel appears in the hardware tree.
4. Highlight the new channel so you can view its properties in the grid.
5. Double-click False to change it to True.
6. The default Controller and Network Timeout values do not need to be changed.
7. Give the communication channel a descriptive name.
8. Click save and the channel settings will be added to the database.
9. Highlight the master PXL in the hardware tree.
10. In the controller properties > Communication Settings > Communications Channel
select the new channel from the drop-down list.
11. A Network channel selection will allow you to then input the IP address for the
LAN-520. The port number is also set to the LAN-520 default of 10001.
12. Click the save icon, within a few seconds events should appear in Live Events sig-
nifying that the master is online.